How to Read Electrical Schematics in Industrial Automation

A practical method for using ladder-style control drawings, wire numbers and cross-references to trace a fault from a PLC output back to the device that failed.

Jobs In Automation Editorial8 min read

Key takeaways

  • Electrical prints are the main troubleshooting tool in automation. Plants that hire techs expect you to trace a circuit across pages without help.
  • Rung numbers run down the left rail; numbers beside a coil on the right point to the rungs where its contacts live, and an underlined number means a normally closed contact.
  • Every contact on a print is drawn in its de-energized shelf state, not the state the machine is in right now.
  • NFPA 79 color conventions help you spot hazards: orange conductors can stay live with the main disconnect off.
  • On IEC-style drawings, coils are A1/A2 and auxiliary contacts follow a two-digit code: 13-14 is normally open, 21-22 is normally closed.

Knowing how to read electrical schematics is the skill that separates an automation technician who swaps parts from one who finds faults. When a machine stops and the HMI only says "Fault: Station 3," the drawings are what get you from that message to the broken limit switch, the loose terminal or the dropped-out relay.

BLS lists reading blueprints, schematics and diagrams among the core duties of electro-mechanical and mechatronics technicians, one of the closest federal occupation codes to automation work. This guide shows you how industrial control drawings are organized and gives you a repeatable way to use them, with the PLC and safety circuits that automation techs see every day.

What Is in a Machine's Drawing Set

The word "schematic" gets used loosely on the floor. A typical machine or panel drawing package contains several kinds of documents, and each answers a different question.

DrawingWhat it showsWhen you use it
Electrical (line) diagram, often ladder-styleHow power and signals flow from sources through control devices to loadsMost troubleshooting: why a motor will not start, why a coil is not pulling in
PLC I/O drawingsEach input and output point, its address, wire number and field deviceMatching what the PLC sees to the real switch, sensor or valve
Panel layoutPhysical location of components and terminal strips in the enclosureFinding the part once you know which part it is
Function block or logic diagramWhat the signals mean and how they combine, not how they are wiredUnderstanding why the sequence works the way it does
Device-level schematicInternal circuitry of a single componentRoot-cause work, such as how a PLC output module switches
P&ID or pneumatic diagramProcess piping, instruments, valves and air circuitsProcess plants and machines with significant air or fluid systems

Control.com makes a useful distinction: function diagrams tell you why a system behaves as it does, while electrical diagrams tell you how it is wired. Names vary from company to company, so learn to recognize what a drawing shows rather than what it is called.

How Ladder-Style Control Drawings Are Organized

Most North American control drawings follow a ladder layout. EC&M's ladder drawing basics lays out the conventions:

  • Rails: two vertical lines carrying control voltage. Fuses, breakers or control contacts may sit on them, and they are often drawn heavier than the rest.
  • Rungs: horizontal lines between the rails. Inputs (switches, contacts) sit on the left of a rung and the output (coil, light, solenoid) on the right.
  • Outputs in parallel: each output gets its own rung. Two loads in series would split the voltage and neither would work properly.
  • Logic by placement: devices in series form AND logic and devices in parallel form OR logic. That is why stop buttons are normally closed and wired in series, while multiple start buttons are normally open and wired in parallel.
  • Page continuations: arrows at the ends of the rails tell you which page the rails continue on.

If you already read PLC ladder logic, this layout will feel familiar, because ladder logic was modeled on these relay drawings. Our ladder logic basics guide covers the software side.

Cross-References and Wire Numbers: How to Read Electrical Schematics Across Pages

A small machine might fit on one page. A production line can run dozens or hundreds. Cross-references and wire numbers are what let you follow a circuit through that stack.

Rung numbers and coil cross-references

Rungs are numbered down the left side of the left rail. To the right of each coil you will usually find a list of numbers. Those point to the rungs where that coil's contacts appear. Per EC&M, a plain number points to a normally open contact, and a number with a line under it points to a normally closed contact.

So if control relay CR5 sits on rung 112 and the right margin shows 118, 124 and an underlined 131, you know CR5 has normally open contacts on rungs 118 and 124 and a normally closed contact on rung 131. When CR5 pulls in, check all three places.

Wire numbers

Each conductor carries a number that ties it to its location on the drawing, and a wire that continues to another page carries a page and line reference to its other end. That number is also printed on the wire marker in the panel, which is how you connect paper to copper. Control.com points out that searching a PDF for a wire number is one of the fastest ways to move around a large set.

Tip: keep a highlighter and a clean printout of the pages for the circuit you are chasing, or use PDF markup on a tablet. Mark the path as you confirm each point with your meter. When you come back after a break, you know exactly where you were.

Contacts, Symbols and the Shelf-State Rule

The single most common reading mistake is forgetting that drawings show devices at rest. Normally open and normally closed describe a device's de-energized, unactuated state. A normally closed stop button is drawn closed, even though on a running machine it is closed and on a pressed one it is open. A limit switch is drawn in its free position, even if the machine sits with a part holding it closed.

Common symbols you will see on control prints:

  • Relay coils drawn as circles labeled CR plus a number, motor starter coils often labeled M
  • Pilot lights as circles with a letter for color
  • Sensors frequently drawn as simple boxes, with the internal electronics left off
  • Contacts as two short parallel lines (open) or the same with a diagonal slash (closed)
  • Overload contacts, fuses, breakers and disconnects in the power section

Expect variation. Machine builders use different CAD libraries, and drawings from overseas builders often use IEC symbols. Eaton publishes a NEMA vs. IEC symbol comparison that is worth printing and keeping in your binder.

Reading IEC-Style Drawings and Terminal Numbers

Many machines in US plants come from European or Asian builders, so you will meet IEC conventions. The terminal numbering is the most useful thing to learn because it is stamped on the devices themselves.

Terminal markingMeaning
A1 / A2Coil terminals on a relay or contactor
13-14First auxiliary contact, normally open
21-22Second auxiliary contact, normally closed
Second digit 1-2Normally closed pair
Second digit 3-4Normally open pair
11 / 12 / 14Changeover contact: common, NC side, NO side

As Control.com's terminal numbering explainer describes it, the first digit identifies which contact set you are on and the second digit identifies its function. Schneider Electric's TeSys D contactors, for example, mark their auxiliary contacts 13-14 for normally open and 21-22 for normally closed. Once this clicks, you can often tell what a contact does just by reading the terminal label, without opening the drawing.

Wire Colors, Control Voltage and Hidden Hazards

Drawings tell you what should be there. Wire colors help you confirm it and warn you about energy you might not expect. According to IEWC's summary of NFPA 79 color practice, industrial machinery typically uses:

  • Green or green/yellow for equipment grounding
  • Red for AC control circuits
  • Blue for DC control circuits
  • Orange for circuits fed from an outside source that stay energized when the main disconnect is off

That orange wire matters. EC&M warns that control voltage can come from a separate source, so turning off the power disconnect may not kill the control circuit. Before you put hands in a panel, find every source on the drawing, not just the main disconnect, and verify with a meter. Older machines and imported equipment may not follow these colors at all, which is one more reason to trust the drawing and your meter rather than the insulation.

A Five-Step Method for Tracing a Fault on the Prints

  1. Start at the symptom. Which output is not doing its job? A motor, a valve, a light? Find its coil or output on the drawing.
  2. Find the PLC point, if there is one. Use the I/O drawings to match the address in the program to the terminal and wire number. Check whether the PLC is turning the output on before you go hunting in the field.
  3. Walk the rung from left to right. Every contact in series must be closed for the output to energize. Use the cross-references to see what controls each contact.
  4. Measure, do not guess. With the circuit safe to test, check voltage at points along the rung. The fault is between the last point where you have voltage and the first point where you do not.
  5. Mark up the drawing. If you find a wire that does not match the print, a jumper nobody documented or a changed device, note it and tell whoever maintains the drawings. Wrong prints cost the next person hours.

That last step is how you build trust on a new crew. Our first year on the automation floor piece covers the rest of that process.

Bottom Line

Reading control drawings is not about memorizing symbols. It is about knowing how a drawing set is organized, using rung and wire numbers to move through it, remembering that every contact is drawn at rest, and recognizing the IEC terminal codes printed on the devices themselves. Practice on a machine that is running fine: pick an output and trace it from the PLC card back to the field device on paper, then confirm it in the panel. Do that a dozen times and the next real breakdown will feel like a familiar exercise.

Gear mentioned in this guide

As an Amazon Associate, Jobs In Automation earns from qualifying purchases. Prices and availability change; check current listings.

Frequently asked questions

What do the numbers next to a relay coil on a ladder diagram mean?

They are cross-references to the rungs where that coil's contacts appear. A plain number points to a normally open contact on that rung, and a number with a line under it points to a normally closed contact. They let you find everything a relay controls without scanning every page of the drawing set.

Are contacts on a schematic shown energized or de-energized?

De-energized. Normally open and normally closed describe a device at rest, with no power on the coil and nothing pressing or actuating it. A stop button is drawn closed and a limit switch is drawn in its free position, regardless of the state the machine happens to be in when you are looking at it.

What do 13-14 and 21-22 mean on a contactor?

They are IEC terminal numbers. The first digit identifies the contact set and the second its function: 3-4 means normally open and 1-2 means normally closed. So 13-14 is the first auxiliary contact, normally open, and 21-22 is the second, normally closed. Coil terminals are marked A1 and A2.

What does an orange wire mean in a control panel?

Under common NFPA 79 practice for industrial machinery, orange marks conductors fed from an external source that can remain energized when the machine's main disconnect is off. Treat any orange wire as possibly live, find its source on the drawings, and verify it is de-energized with a meter before touching it.

Looking for automation work?

Tell us your trade, location and experience. The Careers In Trades network routes you to employers who are actually hiring. Free for workers.

Sources

  1. EC&M — Electrical Ladder Drawing Basics
  2. Control.com — Electrical Drawings, Schematics, and Wiring Diagrams: How to Read Them
  3. Control.com — Info Byte: What's the Reason Behind Relay Terminal Numbering?
  4. IEWC — Control panel wiring color codes and standards
  5. Eaton — Comparison of NEMA and IEC schematic diagrams (MZ081001EN)
  6. Schneider Electric FAQ — TeSys D auxiliary contact terminal numbers
  7. BLS Occupational Outlook Handbook — Electro-mechanical and Mechatronics Technologists and Technicians

Pay, licensing and program details change and vary by state, employer and local agreement. Verify with the linked sources and your state licensing board before making decisions.